system_power.json

The provisioned-power descriptor for one system. One per system, not per point: provisioned power is fixed for the whole curve. Why it exists and what it's used for: What is MLPerf Endpoints?.

Required, and authored by you

Every system needs one. A system without it, or with a file from which no total can be derived, fails the submission checker. Put it at the top level of at least one run folder of the system; the builder places it at results/<system>/system_power.json in the bundle. Authored in step 5.

Fields

The checker reads the shape below. Every field is optional on its own, but the file as a whole has to yield a total.

Field Type Description
provisioned_power_w number A declared total, in watts. If present it is used as-is and the component groups are ignored
rack_power_w, rack_nodes, submitted_nodes number Rack-level node scaling (§4.5.2.1): the published power of a full rack of rack_nodes nodes, scaled to the submitted_nodes you submit
cpu group Host CPUs
accelerator group GPUs, ASICs and similar
compute group Optional. CPU and accelerator as one figure, where the vendor publishes them that way. Replaces cpu and accelerator
scale_up_network group The high-bandwidth fabric between accelerators — NVLink switches, TPU ICI, UALink over Ethernet. Zero in a system with no switches
scale_out_network group Optional. Only for multi-node systems with a scale-out fabric. Reported, but not added to the total
overhead_fraction number Optional, and normally left out: the checker takes it from cooling in system_desc.json (below)

Each group has a count, a rated power per unit in watts, and a link to a public specification. The checker accepts the field names from rules §4.5.2, or a generic spelling on any group:

Group Count Power per unit
cpu num_cpu tdp_per_cpu
accelerator num_accelerator tdp_per_accelerator
scale_up_network, scale_out_network num_switches tdp_per_switch
Any group count tdp_per_unit

The link goes in link or public_specification. Count what's installed, as provisioned, not the chassis maximum.

Declare cooling in system_desc.json

The overhead fraction comes from the system description's cooling field, read at system level or from node_types: 0.30 if it says liquid (or water, or immersion), 0.50 if it says air. A system whose nodes are cooled differently gets 0.50. Without a fraction there is no total, so power-descriptor fails. Passive cooling matches neither value; in that case state overhead_fraction here.

How the total is computed

What the checker computes from the fields above. The power model it implements is in §4.5.2, Power Model.

total_w  = provisioned_power_w                             if declared
         = rack_power_w × submitted_nodes / rack_nodes     else, if all three are given
         = major × (1 + overhead_fraction)                 otherwise

major    = cpu + accelerator + scale_up_network
           (compute replaces cpu + accelerator when given)

provisioned_power_kw = total_w / 1000
system_tps_per_kw    = system_tps / provisioned_power_kw

Scale-out networking isn't part of major. Rules §4.5.2 counts it inside the overhead fraction, along with storage, power-supply overhead and cooling.

Example

A liquid-cooled node with two CPUs, eight accelerators and one scale-up switch. Its system_desc.json says the node is liquid-cooled, so the fraction is 0.30:

{
  "cpu":              { "num_cpu": 2,         "tdp_per_cpu": 350,         "link": "https://vendor.example/cpu-spec" },
  "accelerator":      { "num_accelerator": 8, "tdp_per_accelerator": 700, "link": "https://vendor.example/accel-spec" },
  "scale_up_network": { "num_switches": 1,    "tdp_per_switch": 3500,     "link": "https://vendor.example/switch-spec" }
}

Evidence, partial systems and estimates

These are policy, and live in the rules:

  • Which sources count as evidence for a power figure, and what a component running below its rated TDP has to show: §4.5.2, Methodology.
  • How to state the power of a partially populated system, whether a partial rack, a node with empty accelerator slots, or a system under a TDP cap: §4.5.2.1. Linear scaling is allowed only at whole-node granularity.
  • What MLCommons does with values you leave out, and the "MLC Estimated Power" tag the result then carries: §4.5.2.

Where a published figure is a range, the rules use the upper bound.

The bundle build also fails if two runs of the same system carry different system_power.json contents.

Caveats
  • Scope. Rules §4.5 applies normalization to Standardized CoP and CoN, makes it optional for RDI, and defers Serviced. The same section says every submission must include the file, and the checker requires it for every system regardless of division. Until that's reconciled, include it whatever your division. Tracked as B11.
  • Pending ratification. Tier definitions, overhead fractions, reference components and the metric's name and units are all marked subject to change.

Last verified against: mlcommons/endpoints_policies@v1.0_rules_dev (d2d9da6) and mlcommons/endpoints-submission-cli@main (a42a056, v1.1.0.0), 2026-10-02.